Reefer plugs: the IEC 60309 32 A 3h connector explained

Refrigerated containers plug into ships, terminal racks and generator sets through a red, four-pin industrial plug. It looks like any other 32 A three-phase plug. It is not, and the difference is the position of one pin.

The IEC 60309 plug family in brief

IEC 60309 is the international standard for industrial plugs, socket-outlets and couplers, often called "CEE" or "pin and sleeve" connectors. Three things identify a device in the family:

The clock position is the mechanical key. Two plugs with the same color and rating but a different earth position will not mate, which prevents a device rated for one supply being plugged into another.

Why reefer plugs are "3h"

Most red 3P+E devices you meet on land are 6h, the position IEC 60309-2 assigns to 380–415 V, 50/60 Hz supplies. Reefer plugs use the 3h position. In the clock-position table reproduced by plug maker Mennekes from IEC 60309-2:2023, the 3h position for 3P+E devices is marked as being only for refrigerated containers (ISO standard), for supplies in the 220/380 to 250/440 V range at 50/60 Hz.

3P+E device (red, 32 A)Earth positionTypical use
Standard 400 V industrial6hWorkshops, site supplies, most land-side three-phase equipment
Reefer container3hRefrigerated container power leads, and the matching receptacles on ships, terminal racks, gensets and depot supplies

Reefer plugs and sockets are widely sold as 32 A, 3P+E (four pins), 380–440 V, 3h, red, and in watertight IP67 versions for exposed use. The practical rule: a reefer lead needs a 3h plug, and a reefer supply needs 3h receptacles. A 6h device from a general electrical wholesaler will not mate, and forcing an adapter into the chain removes the protection the keying gives you.

As always, confirm the details against the refrigeration unit maker's documentation and the receptacles at the terminals and on the vessels you use.

Where reefer plugs connect

Gensets commonly deliver 460 V at 60 Hz for the reefer, according to chassis builder CIE Manufacturing's description of how gensets connect. Genset makers' own documentation governs the receptacle and wiring on the genset side.

Choosing a replacement plug

CheckWhy
32 A, 3P+E, red, 3hMust mate with the reefer receptacles you use
Ingress protection (for example IP67)Leads lie on wet quays and decks, and plugs are left unplugged
Cable entry rangeThe gland must seal on the actual outside diameter of your lead
Conductor terminal rangeTerminals must suit the conductor cross-section
Housing materialImpact resistance and cold performance for dropped plugs
Strain reliefLeads are pulled by the cable more often than they should be

Plugs, connectors and receptacles: the terms

IEC 60309 uses precise names for each part, and suppliers' catalogs follow them:

When you order, name the part type as well as the rating and clock position.

Fitting a plug correctly

  1. Prepare the cable to the plug maker's strip lengths, so the gland clamps the sheath, not the cores.
  2. Terminate phases and earth to the marked terminals, with ferrules if the maker calls for them.
  3. Where the maker's instructions call for it, leave the earth conductor slightly longer than the phases, so it is the last to pull free.
  4. Tighten terminals and gland to the specified torque.
  5. Test earth continuity, insulation resistance and phase order before the lead returns to service. Phase order matters, because a reversed rotation affects the refrigeration unit.

Plug fitting on reefer leads is electrical work. Follow your local rules on who may do it and how it is tested.

Common questions

Is a reefer plug the same as a standard red 32 A plug?

No. Both are red, 32 A, 3P+E, but a standard land-side plug normally has its earth at 6h and a reefer plug at 3h, so they do not mate.

What voltage do reefer containers use?

Reefer units run on three-phase AC. Supplies of 380–460 V are common, and gensets commonly supply 460 V at 60 Hz. The unit maker's documentation states what a particular unit accepts.

Can I use a 6h-to-3h adapter?

An adapter defeats the keying that stops a device being plugged into the wrong supply. Use 3h receptacles where reefers are powered, and have any installation designed by a qualified electrician.

Why do reefer plugs fail?

They are dropped, dragged, run over and left open to the weather. Cracked housings, bent pins and water in the plug are the common faults. See reefer container power cables for the lead itself.

What to send a supplier